How to choose a reasonable diesel generator capacity?
With the development of the economy and the increase in electricity demand, diesel generators are increasingly used in various fields. However, many electrical designers are often confused when selecting the capacity of a diesel generator. We all know that there are many factors to consider when choosing a reasonable diesel generator capacity. Only by comprehensively considering factors such as power demand, load nature, importance of power demand, environmental factors, and economy can you choose the most suitable diesel generator for you. So in the electrical design of civil buildings, how should we reasonably choose the capacity of diesel generators? You can choose the diesel generator according to the following actual usage conditions of the project.
- In case of a power outage
When the mains power is out, the diesel generator should be able to supply the first and second-level loads of the project. Therefore, in this case, the diesel generator capacity should be selected according to the first and second-level load capacity of the project. Assume that the total capacity of the primary and secondary loads of the project is P1. (If the project has two 10kV power incoming lines, then P1 does not include the secondary load in the project.)
- In case of fire
When a fire occurs, the diesel generator should be able to supply the fire load of the project. Assume that the fire load capacity of the project is P2. If P2<P1, then the diesel generator capacity should be selected based on P1; if P2>P1, then the capacity of the diesel generator needs to be selected based on the ground load. Calculate the larger of the fire-fighting equipment capacity that needs to be put into operation in the case of a fire in the largest building or a fire in the basement. Assume that its capacity is P2', then compare P2' with P1, and choose the larger one to choose diesel. Generator capacity. The diesel generator capacity selected in this way is more reasonable.
If the fire water pump or fan in the project has a large capacity, it is also necessary to review whether the diesel generator capacity selection can meet the starting conditions of the largest fire water pump or fan. If not, the diesel generator capacity needs to be increased accordingly.
- In case of special electricity demand
In addition to the above three usage situations, if the builder has special power needs, then the capacity of the diesel generator needs to be selected according to the builder's power needs.
In addition, in the event of a fire, the diesel generator should be designed to automatically cut off non-fire-fighting important loads to ensure that the diesel generator has sufficient power supply capacity and reliably supplies power to the fire-fighting loads.