Products

Generac 140kw-300kw Diesel Generator
Cooling System: Air-cooled and naturally Aspiration
Alternator Type: Self-excitation, Brushless Type
Starting: DC 12V Electronic Start
Engine Type: 4-cylinder,4-Stroke
Features
Generac 140kw-300kw Diesel Generator Product Introduction
Generac 140kw-300kw Diesel Generator is a powerful and reliable solution for your energy needs. Made with high-quality materials and innovative technology, this diesel generator ensures uninterrupted power supply even in the toughest conditions. With a power output range of 140kw-300kw, this generator is capable of meeting the demands of large industrial and commercial facilities. No matter what your energy requirements are, this generator has got you covered. Generac 140kw-300kw Diesel Generator is known for its durability and longevity. It has been designed to withstand extreme weather conditions, making it the perfect choice for use in harsh environments. The generator is also equipped with advanced safety features that prevent accidents and protect the environment.
What's more, the Generac 140kw-300kw Diesel Generator is highly fuel-efficient, which translates to lower operating costs. This means you can enjoy an uninterrupted power supply without worrying about fuel expenses.
Generac 140kw-300kw Diesel Generator Product Specification

A diesel generator is a kind of small power generation equipment, which refers to the power machinery that uses diesel as fuel and a diesel engine as the prime mover to drive the generator to generate electricity. The entire unit generally consists of a diesel engine, generator, control box, fuel tank, battery for starting and controlling, protection device, emergency cabinet, and other components.
Common faults and troubleshooting methods of diesel generators
1:Engine power is insufficient. Common causes include poor fuel quality or water in the fuel, low fuel pressure, air leakage in the intake system, etc.
Method of exclusion:
(1) Drain the fuel from the fuel tank, replace it with a new fuel filter, and inject clean fuel.
(2) Make sure there is fuel in the fuel tank, and check whether there is any oil leakage or bending in the oil pipe between the fuel tank and the fuel transfer pump. Check whether there is air in the fuel system and whether the fuel bypass valve is stuck, and then check the fuel pressure. At full load speed, the outlet pressure of the fuel transfer pump must be a minimum of 415 kPa, and the pressure in both fuel manifolds must be 415 to 450 kPa. If the fuel pressure is lower than the above pressure, the filter should be replaced. If the fuel pressure is still low, check the fuel transfer pump and the fuel pressure regulator valve on the fuel manifold.
(3) Check the pressure in the intake manifold and see if there is any obstruction in the air filter.
2: The engine vibrates excessively after starting. Common causes include loose or faulty shock absorbers, loose engine mounts, misalignment or imbalance of driven equipment, etc.
Method of exclusion:
(1) Check whether the shock absorber is damaged and tighten each bolt. If the bolt holes of the shock absorber are damaged, replace them with new ones.
(2) Check the alignment and balance, and make corrections if necessary.
3:There is coolant in the lubricating oil. Common causes include damaged oil cooler core, damaged cylinder head gasket or water seal, cracked cylinder head, etc.
Method of exclusion:
(1) Replace with new oil cooler core and oil filter, and inject clean lubricant.
(2) Check the protruding part of the cylinder liner flange, install a new water seal in the partition, and tighten the bolts used to fix the cylinder head according to the technical specifications. Replace with new cylinder head.
4:Generator overheated. Common causes include long-term engine overloading, blockage of ventilation ducts, etc.
Method of exclusion:
(1) The engine is overloaded for a long time. You should always pay attention to the instruments on the dashboard such as power, power factor, and current to avoid overloading.
(2) If the ventilation duct is blocked, the inside of the generator should be completely blown out.

FAQ
Q: What is the average fuel consumption per hour of the generator?
A: The average fuel consumption per hour of the Generac 140kw-300kw Diesel Generator varies depending on the load. However, it is generally very fuel efficient.
Q: What safety features does the generator have?
A: The Generac Diesel Generator has several safety features such as low oil pressure shutdown, high coolant temperature shutdown, and emergency stop button.
Q: What is the noise level of the generator?
A: The noise level of the Diesel Generator varies depending on the load but it is generally quiet and operates at a noise level of around 70 decibels.
Q: Does the generator come with an automatic transfer switch?
A: No, the automatic transfer switch is sold separately.
Hot Tags: generac 140kw-300kw diesel generator, China generac 140kw-300kw diesel generator manufacturers, suppliers, Useful Black Standby Diesel Generator, Industrial Long Lasting Diesel Generator, Large Efficient Diesel Generator, Industrial Long Lasting Diesel Generator, Canopy Diesel Generator, Generator
You Might Also Like